Realarm Feature: Normally programming requires the audible alarm to sound whenever a new alarm condition is received.
Lamp Outputs: 128 discrete lamp driver outputs. Each output is capable of driving up to 4 lamps simultaneously. Any color lamp can be connected to any output.
Lamp Control:
Relationship of input conditions to lamp illumination is controlled by the one-chip microcontroller. Each operation is controlled by a preprogrammed operational scenario. Contact the factory for the description of each of the currently available scenarios. Custom programming is available to meet your unique application. Contact the factory for details.
Audible Alarms: Three separate audio outputs with volume control are available. Each output is programmable. Current outputs are
- Steady tone: 1000 Hz.
- Interrupted tone: 1000 Hz., 50% duty cycle. 1 cycle per second.
- Warble tone: 1000 Hz. center freq., 250 Hz deviation.
Power Requirements: 12VDC, 1.8 amps. (max) provided by external UL-listed, wall-mounted transformer. Backup battery optional.
Size:
GDI circuit board; 6" W x 12" L (approx. 1-1/4-inch component height) Paddle board terminal strip, 64 terminals each, 2 required for 128 inputs; 3" W x 8" L
Weight: Circuit board 1 lb.
|